Chapter 6 Stabilizing the Cabinet
NOTE For seismic installations, you MUST order and install a Powerware 9155 UPS seismic kit; do not use the following instructions.
NOTE For
To stabilize the cabinet(s):
1.Lower the leveling feet to prevent the cabinet from rolling.
Figure 22. Lowering the Leveling Feet
2.Attach the stabilizing bracket to the bottom of the cabinet rear panel using the retained hardware from the shipping pallet according to the cabinet configuration:
S For one cabinet, see Figure 23.
S For two cabinets, see Figure 24.
S For three cabinets, see Figure 25.
NOTE No more than three cabinets can be attached together. For four cabinets, use two of the
3.Use the holes and slots in the bottom of the bracket to attach the cabinet to the flooring if desired.
EATON Powerware® 9155 Parallel UPS | 31 |