OPERATION

User Settings

The following table displays the options that can be changed by the user.

NOTE Changes to the output voltage or frequency options should be made before turning on the UPS; otherwise, the changes do not take effect.

Table 4. User Settings

Description

Available Settings

Default Setting

 

 

 

 

 

Set Date and Time

Set Month

01/01/2003

 

 

Date: mm/dd/yyyy

 

 

Time: 24:00

00:00

 

 

 

 

Display Contrast

Adjust contrast with up/down arrow buttons

Moderate

 

 

 

Change Language

Select Language: <English>

English

 

Elegir idioma <Español>

 

 

 

 

 

 

Relay Config

Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or

 

[X-Slot 2-1/2/3/4]

 

Setup: [empty] [On Battery] [summary alarm]

 

[On Bypass] [UPS ok] [custom]

Alarm 1: empty X-Slots (1 or 2) #1: UPS ok #2: On Bypass

#3: Summary Alarm

#4: On Battery

Signal Inputs

[empty] [Logic]

 

<empty>

 

Signal Input must be wired to the CAN Bridge

 

 

Card (see Figure 19 on page 27).

 

 

 

For more information, refer to “Programmable

 

 

Signal Inputs” in the Powerware 9155 UPS

 

 

(8–15 kVA) User’s Guide.

 

 

 

 

 

 

 

 

Serial Port Config

Port: [X-Slot-1] [X-Slot-2/Serv]

 

19200

 

Speed: [19200] [9600] [2400] [1200]

 

 

 

 

 

 

 

Parallel Operation Settings

Parallel Unit Number: [Single Unit] [Unit #1]

Single Unit

 

[Unit #2] [Unit #3]

 

 

 

 

 

 

 

 

 

Start Auto Calibration: [Press

 

 

]

 

 

 

 

 

 

 

 

 

 

Redundant Mode

 

Redundant Mode

 

Capacity Mode

 

 

 

 

 

 

 

 

42

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com