OPERATION

Table 4. User Settings (continued)

Description

Available Settings

Default Setting

 

 

 

 

 

Modem Config

Modem Installation

<Not Installed>

 

 

 

 

 

 

Set Modem Call Events

Event #0

 

 

 

Call modem: no

 

 

 

 

 

 

Set Modem Init String

ATZ0

 

 

 

 

 

 

Set Modem Call Command

None

 

 

 

 

 

 

Set Modem Communication Password

None

 

 

 

 

 

Start Screen

Eaton Powerware logo

Eaton Powerware logo

 

 

Mimic screen

 

 

 

 

 

 

User Password

Enabled/Disabled

Disabled

 

 

If Enabled is selected, the password is USER.

 

 

 

 

 

 

Audible Alarms

Normal Sound/Disabled

Normal Sound

 

 

 

 

 

Battery Charging

ABM cycling/constant

ABM cycling

 

 

 

 

 

Automatic Battery Tests

Enabled/Disabled

Enabled

 

 

Enabled automatically runs the battery test

 

 

 

once a month.

 

 

 

 

 

 

Full Power Battery Test

Enabled/Disabled

Enabled

 

 

 

 

 

Number of Battery Strings

0 through 22

2 strings for UPS-32 models

 

 

(see “Configuring the UPS for EBMs” on

4 strings for UPS-64 models

 

 

page 49)

 

 

 

 

 

 

Battery Capacity

1 through 65535 watts per cell

34 W/cell

 

 

 

 

 

Battery Low Alarm Level

1.750 through 1.950 volts per cell

1.880 V/cell

 

 

 

 

 

Set Nominal Output Voltage

120V/240V

120V/208V

 

 

120V/208V

 

 

 

110V/220V

 

 

 

100V/200V

 

 

 

127V/220V

 

 

 

 

 

 

Bypass Voltage High Limit

+1 through +20% (1% increments)

120V +10%

 

 

 

 

 

Bypass Voltage Low Limit

-1 through -20% (1% increments)

120V -15%

 

 

 

 

 

Nominal Output Frequency

50 Hz or 60 Hz

60 Hz

 

 

 

 

 

Synchronization

Enabled/Disabled

Enabled

 

 

 

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com