OPERATION

6.Configure the UPS for parallel operation through the front panel:

SPress any button on the front panel display to activate the menu options.

S Using the button, scroll to the Settings menu, and then press the button twice to select the User Settings menu.

SUsing the button, scroll to the Parallel Operation Settings option and press the button.

SPress the button to select the Parallel Unit Number option.

SUse the button to scroll the Unit number to identify the UPS number of the parallel system (Unit #1, Unit #2, or Unit #3).

SPress the button to save the setting.

SUse the button to scroll to the Parallel Operation Mode option and press the button to enter the menu.

SUse the button to scroll the desired option (either Redundant Mode or Capacity Mode).

S Press the button to save the setting.

7.Press the ESC button until the Eaton Powerware logo appears.

8.Repeat Steps 6 and 7 for the remaining UPSs in the parallel system.