C H A P T E R 2

INSTALLATION SETUP

This chapter explains how to setup and install the Powerware 9170 cabinets:

￿Unpacking and setup, including clearances and location requirements

￿Caster cart installation

￿Stabilizer bracket installation (for 12-slot cabinets with non-isolated output)

￿Rack-mount installation

￿Floor anchor kit installation

￿Moving the cabinets

Equipment Clearances

All cabinet sizes require the following clearances to allow for servicing and adequate ventilation:

￿From the side panels: 6￿ (15.2 cm)

￿Top and back: 12￿ (30.5 cm)

￿Front: 36￿ (91.5 cm)

If flexible conduit connects the UPS to the service input and load distribution panels, you may be able to gain access for servicing by moving the UPS. If this is the case, you must still leave 12￿ (30.5 cm) clearance at the back and 6￿ (15.2 cm) at the sides of the UPS for ventilation.

NOTE Do not block the ventilation holes on each side and the back of the unit.

Nine- and 12-slot external battery cabinets may be installed with bases tight against the UPS cabinet base and against each other. Six-slot cabinets require 6￿ of separation.

Powerware® 9170 User's Guide ￿ LTM-1344 B Uncontrolled Copy

7