Electrical Installation
Input Current RatingsTable 1 contains the required circuit breaker ratings for hardwired installations. Circuit breaker ratings for units having an input line cord are determined by the current capacity of the line cord.
Table 1. Required Input Circuit Breaker Sizes (200240 Vac, 50/60 Hz)
UPS Capacity | Circuit Breaker Rating |
|
|
|
|
3 kVA | 25A |
|
|
|
|
6 kVA | 40A |
|
|
|
|
9 kVA | 60A |
|
|
|
|
12 kVA | 80A |
|
|
|
|
15 kVA | 100A |
|
|
|
|
18 kVA | 125A |
|
|
|
|
|
|
|
NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation of the Powerware 9170 UPS contain wiring to support the maximum capacity of the UPS cabinet: 3 kVA for
See Table 2 for recommended conductor sizes to wire the input circuit breakers.