Battery Cabinet Installation
Cable Assembly
Figure 16. Battery Cable Assembly Installation
12.Align the screw holes of the cable assembly's entry plate with holes on the cabinet side panel as shown in Figure 16. Secure the entry plate with screws supplied with the cable assembly.
13.If the battery cable will be installed in
14.Secure the cable assembly terminals by tightening the nuts onto the backplane bus bars. Also tighten the third nut, holding the other fuse end. Torque all three nuts to 7585 in lb
(8.59.6 Nm).
15.Replace the UPS cabinet rear panel with the screws removed in Step 2 on page 17.
16.If the battery cable will be installed in flexible or other conduit, pull the conductors through the conduit. Attach the conduit to both the UPS power entrance panel and the battery cabinet entrance panel as shown in Figure 17.
20 | Powerware® 9170 User's Guide |