
UPS Startup
4.The output voltage is the most important operating parameter you must set as part of the initial configuration screens. Select the desired UPS output voltage using the and buttons.
Possible selections are 200, 208, 220, 230, and 240 Vac. (Low voltages are derived from these voltages, as listed in Table 5 on page 35 and Table 6 on page 43.) Press the button when the desired output value is displayed.
5.If the system includes any external battery cabinets, record the
External Capacity
extamphr 0028.8
<± ±> ESC
6.The system signals an alarm when required output cannot be maintained with the loss of redundant power modules. The alarm is essentially disabled with a redundancy level set at 0.
If you want the system to notify you when the number of redundant power modules is less than a specified level, enter a redundancy level. Each increment above 0 indicates the number of modules that can be removed from operation before the alarm occurs. This setting only affects the alarm; the system continues to operate as an N+X system even if this parameter is left at the default value of 0.
Set Redundancy
RSetting 0
<± ±> ESC
Powerware® 9170 User's Guide | 57 |