Electrical Installation
Table 3. Bypass Switch Positions
Switch Position | Description |
|
|
LINE | Connects the load directly to AC input power and disconnects UPS output. AC input power is still |
| connected to the UPS input. |
|
|
OFF | Disconnects the load from the UPS output power and AC input power, as well as AC input power |
| to the UPS input. |
|
|
UPS | Connects the UPS output to the load. |
|
|
SERVICE | Like the LINE position, SERVICE connects the load directly to AC input power and disconnects |
| UPS output. However, because SERVICE also disconnects AC input from the UPS, this is |
| the appropriate position for UPS maintenance or repair. |
|
|
| To disconnect AC input power during maintenance or service, turn the |
| bypass switch to the SERVICE position. For MBB switches, you must |
| press the red button beside the switch before you can change the switch |
| position. |
| There are six bypass switch models available for the Powerware 9170 |
| UPS as specified in Table 4. |
Table 4. Bypass Switch Specifications
Bypass Switch Models |
|
| See Figure 20 |
|
| ||||
|
| Rating, |
|
|
|
|
| Weight | |
BBM | MBB | Height | Width | Depth | Mounting Centers | ||||
Continuous | |||||||||
| |||||||||
|
|
|
|
|
|
|
| ||
|
|
| (A) | (B) | (C) | (D) | (E) |
| |
|
|
|
|
|
|
|
|
| |
BPE12BBM1A | BPE12MBB1A | 40A/300 Vac | 21.0 | 14.0 | 6.8 | 11.0 | 20.0 | 27 lb | |
|
| (CSA) | (534 mm) | (356 mm) | (172 mm) | (280 mm) | (508 mm) | (12.3 kg) | |
|
| 50A/300 Vac |
|
|
|
|
|
| |
|
| (UL,TÜV) |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
BPE14BBM1A | BPE14MBB1A | 80A/300 Vac | 21.0 | 14.0 | 6.8 | 11.0 | 20.0 | 31 lb | |
|
|
| (534 mm) | (356 mm) | (172 mm) | (280 mm) | (508 mm) | (14.1 kg) | |
|
|
|
|
|
|
|
|
| |
BPE22BBM1A | BPE22MBB1A | 150A/300 Vac | 26.5 | 18.4 | 6.6 | 16.0 | 25.5 | 53 lb | |
|
|
| (673 mm) | (467 mm) | (168 mm) | (406 mm) | (648 mm) | (24.1 kg) | |
|
|
|
|
|
|
|
|
|
28 | Powerware® 9170 User's Guide |