C H A P T E R 5

ISOLATED OUTPUT WIRING DIAGRAMS

The wiring diagrams in this section are unique and specific to installations in which the output of the Powerware 9170 UPS is galvanically isolated from the input.

Figure 37 through Figure 40 describe output wiring configurations for various output voltages. Use Table 6 to find the desired wiring diagrams and connect the output AC wiring to the proper Powerware 9170 system power terminals. You must also set the operating menu parameter 7-3-4 for the required output voltage as shown in the wiring configuration drawings.

NOTE For isolated outputs, all power modules in the Powerware 9170 UPS cabinet must be split-phase modules, which have blue labels.

NOTE In isolated-output installations, connect the UPS green and yellow neutral-to-ground wire (N-G bond) to UPS output terminal as illustrated in Figure 36 on page 45.

Table 6. Wiring Diagrams for Isolated Output

UPS Input

UPS Output

 

External

 

Wiring Diagrams

 

 

Output Wires

 

 

 

 

 

Voltage

Voltage

Bypass

Input

Output

 

System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100/200

100/200

 

Yes

Figure 25a

Figure 34

Figure 37

 

110/220

110/220

 

 

 

 

 

 

 

 

 

115/230

115/230

L1, L2, N*

 

 

 

 

 

 

 

 

 

 

 

 

120/240

120/240

 

No

Figure 25a

Figure 34

Figure 38

 

120/208**

120/240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120/208**

120/208

L1, L2, N*

Yes

Figure 25a

Figure 35

Figure 39

 

 

 

 

 

 

 

127/220**

127/220

No

Figure 25a

Figure 35

Figure 40

 

 

 

*Split-phase power modules required.

**External bypass switch, if installed, must be Break-Before-Make.