Specifications

Table 12. Isolation

Model 0650C Output

±3% load regulation (under any line, load, or battery condition)

Neutral-to-Ground Bonding

Neutral is carried through from input to output; a separate neutral-to-ground bond is

 

not required

 

 

Model 0650I Isolation, Including

True, separately-derived power source as defined by National Electrical Code

Output Neutral-to-Ground

Article 250-5d, with output neutral bonded to ground. No direct connection between

Bonding

input and output; neutral-to-ground bond is required; other local codes may take

 

precedence.

 

 

Table 13. Model Specifications

kVA

Watts

Input Current for

Output Current for

Recommended

Heat Dissipation

 

 

208/220/230/240V*

208/220/230/240V

Input Service*

Double-Conversion Mode

 

 

 

 

 

 

 

 

3

2100

17/16/15/15A

 

14.4/13.6/13.0/12.5A

25A

285W

(0.98 kBTU/hr)

 

 

 

 

 

 

 

 

6

4200

31/29/28/27A

 

28.8/27.2/26.0/25.0A

40A

570W

(1.95 kBTU/hr)

 

 

 

 

 

 

 

 

9

6300

46/44/42/41A

 

43.2/40.8/39.0/37.5A

60A

860W

(2.93 kBTU/hr)

 

 

 

 

 

 

 

 

12

8400

62/59/56/53A

 

57.6/54.4/52.0/50.0A

80A

1145W

(3.90 kBTU/hr)

 

 

 

 

 

 

 

 

15

10500

77/73/70/67A

 

72.0/68.0/65.0/62.5A

100A

1430W

(4.88 kBTU/hr)

 

 

 

 

 

 

 

 

18

12600

93/87/84/80A

 

86.4/81.6/78.0/75.0A

125A

1720W

(5.85 kBTU/hr)

 

 

 

 

 

 

 

 

 

 

Voltages Only Available with Split-Phase Modules

 

 

 

 

 

 

 

 

 

kVA

Watts

Input Current

 

Output Current for

Recommended

Heat Dissipation

 

 

for 200V*

100/200V, 110/220V, 120/240V

Input Service*

Double-Conversion Mode

3

2100

18A

 

30/15A, 27/14A, 25/12.5A

25A

285W

(0.98 kBTU/hr)

 

 

 

 

 

 

 

 

6

4200

32A

 

60/30A, 54/28A, 50/25A

40A

570W

(1.95 kBTU/hr)

 

 

 

 

 

 

 

 

9

6300

48A

 

90/45A, 81/42A, 75/37.5A

60A

860W

(2.93 kBTU/hr)

 

 

 

 

 

 

 

 

12

8400

64A

 

120/60A, 108/56A, 100/50A

80A

1145W

(3.90 kBTU/hr)

 

 

 

 

 

 

 

 

15

10500

80A

 

150/75A, 135/70A, 125/62A

100A

1430W

(4.88 kBTU/hr)

 

 

 

 

 

 

 

 

18

12600

100A

 

180/90A, 162/84A, 150/75A

125A

1720W

(5.85 kBTU/hr)

 

 

 

 

 

 

 

 

 

*For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module.

78

Powerware® 9170 User's Guide ￿ LTM-1344 B Uncontrolled Copy