
Isolated Output Wiring Diagrams
50 or 60 Hz
100/200, 110/220, 115/230, or 120/240V Out
with Isolated Output Option
Parameter 7-3-4 set to 200, 220, 230, or 240, as required.
X1 | X3 | X0 | | | X2 |
X | | | X | X |
| | | | N-G Bond | | |
| | | | | | | | | | |
| | | | | | | | | | |
| | | 100, 110, | | 100, 110, | | | |
| | | 115, or 120 | | | 115, or 120 | | |
| | | | | | | | | | | |
| | | 200, 220, 230, or 240 | | |
| | | | |
L1 | | | N | L2 |
Figure 34. Isolated Outputs Single-Phase Voltages
50 or 60 Hz
120/208 or 127/220V Out
with Isolated Output Option
Parameter 7-3-4 set to 208 or 220, as required.
X1 | X3 | | | X0 | | X2 |
| X | | | X | | | X |
| | | | | N-G Bond |
| | | | | | | | | |
| | | | | | | | | |
| | | | 88 or 93 | | 120 or 127 | | |
| | | | | | | | | | | |
| | | | | | | | | | | | |
| | | | | 208 or 220 | | |
| | | | | |
| L1 | | | N | | | L2 |
Figure 35. Isolated Outputs Derived 3-Phase Voltages
Neutral-to-Ground Bonding for Isolated OutputAs required under safety regulations issued by various regulatory agencies, the UPS cabinet must have a ground-bond connection for the neutral terminal of an isolated-output system. In such a system, the customer must make the neutral-to-ground (also referred to as N-G or neutral-to-earth) connection after selecting the desired output configuration.
In isolated-output systems, a green and yellow neutral-to-ground bonding wire is supplied, with one end connected to the ground (earth) UPS terminal as shown in Figure 36. The other end of the wire (as shown by * in Figure 36) must be attached to the proper output neutral terminal, as specified in Figure 34 and Figure 35.
44 | Powerware® 9170 User's Guide LTM-1344 B Uncontrolled Copy |