Communication
Pin | Function | Description |
|
|
|
5 | A normally open contact that closes (pulls to Common) to signal a Near Low Battery or | |
| Low Runtime alarm. Values that affect this contact closure may be | |
| Contact* |
|
|
|
|
6 | Reserved | Reserved |
|
|
|
7 | Immediate Shutdown | Set by External Shutdown parameter, n = 0: |
| Mode | Grounding this pin for 5 seconds causes the UPS to switch immediately to the Off |
|
| mode. When AC input power returns, the UPS will not restart without user intervention. |
Remote Shutdown Mode
Set by External Shutdown parameter, n = 1 or greater:
In battery operation, grounding this pin for 5 seconds causes the UPS to shut down after a delay of X minutes, regardless of the return of AC input power. This time is defined by the External Shutdown mode parameter n, where n and X are related as follows:
n | X | n | X |
1 | 2 | 4 | 5 |
2 | 1 | 5 | 10 |
3 | 3 | 6 | 20 |
8 | A normally closed contact that opens (releases from Common) 15 seconds after the UPS | |
| switches to battery power. | |
|
|
|
9 | A normally open contact that closes (pulls to Common) whenever the UPS is in internal | |
| bypass mode or is being externally bypassed and is being signalled of the external | |
| Contact* | bypass. |
*Contacts consist of
72 | Powerware® 9170 User's Guide |