03 --Reserved--

 

Reserved

 

 

 

 

 

 

 

 

4

04 I Out 3.1

Service

acampsiout

The current your equipment is drawing from

 

 

 

 

(o)

the UPS.

 

 

 

 

 

 

 

5

05 VA Out 374

Change Not

vaout

Volt-Amps Out. The total “apparent power”

 

 

 

Allowed

(va)

your equipment is drawing from the UPS.

 

 

 

 

 

This value is based on parameter 2 multiplied

 

 

 

 

by parameter 4, and should be less than or

 

 

 

 

 

equal to the VA or kVA rating of the UPS. See

 

 

 

 

VA Limit, parameter 19.

 

 

 

 

 

 

6

06 I Batt 0.0

Service

ibatt

Battery Current. When the UPS is running on

 

 

 

(ib)

AC input, this is the charging current inA.

 

 

 

 

 

When the UPS runs on battery power

 

 

 

 

 

(inverter), this is the amount of current (inA)

 

 

 

 

 

the batteries are supplying to the UPS.

 

 

 

 

 

 

 

7

07 V Batt 48.51

Service

vbatt

Battery Volts. The present battery voltage.

 

 

 

 

(vb)

The UPS sounds an alarm if this value is too

 

 

 

 

 

low.

 

 

 

 

 

 

 

8

08 Freq 60.43 Hz

Change Not

frequency

In normal operation, this is the frequency of

 

 

 

Allowed

(f)

power the UPS is receiving from the AC input

 

 

 

 

source. If this value falls outside preset

 

 

 

 

 

limits, the UPS goes to battery power. When

 

 

 

 

the UPS is running on battery power, this is

 

 

 

 

 

the frequency the UPS is supplying to your

 

 

 

 

 

equipment.

 

 

 

 

 

 

 

9

09 RunTime 12m

Change Not

runtime

Estimated Runtime Remaining. The amount

 

 

 

Allowed

(rt)

of time the UPS continues to support your

 

 

 

 

 

equipment when the UPS is running on

 

 

 

 

 

battery power. The UPS sounds an alarm

 

 

 

 

 

when this value falls below a preset limit.

 

 

 

 

 

 

 

10

10 Date 06/01/93

None

date

System Date. The UPS uses this date to

 

 

 

 

(d)

record alarms and inverter runs. The date

 

 

 

 

 

must be reset when you restart the UPS after

 

 

 

 

DC power is turned off.

 

 

 

 

 

 

 

11 or

11 Amb Temp 23c

Change Not

ambtemp

The temperature (in Celsius) inside the UPS.

 

[DISPLAY]

 

Allowed

(at)

The UPS sounds an alarm and shuts down if

 

[1] [1] [ENTER]

 

 

 

this value is too high.

 

 

 

 

 

 

 

12

12 SinkTemp 26c

Change Not

heatsinktemp

The temperature of the heatsink. The UPS

 

 

 

Allowed

(st)

sounds an alarm if this value is too high.

 

 

 

 

 

 

 

13

13 --Reserved--

 

Reserved

 

 

 

 

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

33

Page 39
Image 39
Powerware FE/QFE UPS manual Ups, VA Limit, parameter, Low, DC power is turned off, This value is too high