o | r c | o | o m | d |
|
m |
|
| 3r e4 |
|
|
3 | 03 |
| Reserved |
|
|
|
|
|
|
|
|
4 | 04 I Out 3.1 | Service | acampsiout | The current your equipment is drawing from |
|
|
|
| (o) | the UPS. |
|
|
|
|
|
|
|
5 | 05 VA Out 374 | Change Not | vaout |
| |
|
| Allowed | (va) | your equipment is drawing from the UPS. |
|
|
|
|
| This value is based on parameter 2 multiplied | |
|
|
|
| by parameter 4, and should be less than or |
|
|
|
|
| equal to the VA or kVA rating of the UPS. See | |
|
|
|
| VA Limit, parameter 19. |
|
|
|
|
|
| |
6 | 06 I Batt 0.0 | Service | ibatt | Battery Current. When the UPS is running on | |
|
|
| (ib) | AC input, this is the charging current inA. |
|
|
|
|
| When the UPS runs on battery power |
|
|
|
|
| (inverter), this is the amount of current (inA) |
|
|
|
|
| the batteries are supplying to the UPS. |
|
|
|
|
|
|
|
7 | 07 V Batt 48.51 | Service | vbatt | Battery Volts. The present battery voltage. |
|
|
|
| (vb) | The UPS sounds an alarm if this value is too |
|
|
|
|
| low. |
|
|
|
|
|
|
|
8 | 08 Freq 60.43 Hz | Change Not | frequency | In normal operation, this is the frequency of |
|
|
| Allowed | (f) | power the UPS is receiving from the AC input | |
|
|
|
| source. If this value falls outside preset |
|
|
|
|
| limits, the UPS goes to battery power. When | |
|
|
|
| the UPS is running on battery power, this is |
|
|
|
|
| the frequency the UPS is supplying to your |
|
|
|
|
| equipment. |
|
|
|
|
|
|
|
9 | 09 RunTime 12m | Change Not | runtime | Estimated Runtime Remaining. The amount |
|
|
| Allowed | (rt) | of time the UPS continues to support your |
|
|
|
|
| equipment when the UPS is running on |
|
|
|
|
| battery power. The UPS sounds an alarm |
|
|
|
|
| when this value falls below a preset limit. |
|
|
|
|
|
|
|
10 | 10 Date 06/01/93 | None | date | System Date. The UPS uses this date to |
|
|
|
| (d) | record alarms and inverter runs. The date |
|
|
|
|
| must be reset when you restart the UPS after | |
|
|
|
| DC power is turned off. |
|
|
|
|
|
|
|
11 or | 11 Amb Temp 23c | Change Not | ambtemp | The temperature (in Celsius) inside the UPS. |
|
[DISPLAY] |
| Allowed | (at) | The UPS sounds an alarm and shuts down if |
|
[1] [1] [ENTER] |
|
|
| this value is too high. |
|
|
|
|
|
|
|
12 | 12 SinkTemp 26c | Change Not | heatsinktemp | The temperature of the heatsink. The UPS |
|
|
| Allowed | (st) | sounds an alarm if this value is too high. |
|
|
|
|
|
|
|
13 | 13 |
| Reserved |
|
|
|
| ||||
Powerware® FERRUPS FE/QFE UPS (500 | 33 |