User Test

The user is testing the alarm feature.

To start the user test alarm from the

 

 

Alarm

 

control panel, press [CTRL]-[8] [ENTER]

 

 

 

 

[ENTER]. Repeat the procedure to turn the

 

 

 

 

alarm off.

K

:

Hi

The transformer temperature is too high. If

 

 

Transfmr

the temperature reaches a preset point, the

 

 

Temp

UPS shuts down.

The UPS may have shut down; if so, contact your service representative. If the UPS has not shut down, shut down your equipment or bypass the UPS; then, turn the UPS off and contact your service representative.

L

: : :

Check

The UPS has detected a charger problem.

Contact your service representative.

 

 

Charger

 

 

 

 

 

 

 

M

– –

Check

The batteries have failed the automatic

Contact your service representative.

 

 

Battery

system test.

 

 

 

 

 

 

N

:

Check

The inverter has failed the automatic

Contact your service representative.

 

 

Inverter

system test.

 

 

 

 

 

 

O

– – –

Memory

Possible microprocessor problem.

Shut down your equipment or bypass the

 

 

Check

 

UPS; turn off the UPS. Contact your service

 

 

 

 

representative.

P

: :Emergency

The Remote Shutdown feature has been

 

PwrOff

activated at the RS-232 port (see “Remote

 

 

Shutdown” on page 47.)

To restart the UPS, disconnect the signal to Pin 21 on the RS-232 port. If you have a control panel, put the UPS in Auto mode. If not, turn the On/Off switch off and then on again.

Q

:

Hi PFM

The Power Factor Module’s temperature is

 

 

Res

too high. If the temperature reaches a

 

 

Temp

preset point, the UPS shuts down.

If the UPS has shut down, contact your service representative. If not, shut down your equipment or bypass the UPS; then, turn the UPS off and contact your service representative.

R

: :

Probe

A temperature probe is missing or

The UPS may shut down. Contact your

 

 

Missing

damaged.

service representative.

 

 

 

 

 

S

: : :

High AC

The input voltage is higher than the alarm

Contact your service representative.

 

 

Input

setting.

 

 

 

 

 

 