Table 6. DB-25 Port Settings

r

r r

W

 

 

 

Connector

25 pin D (female) wired as DCE.

 

Format

ASCII, 8 bits, 1 stop bit.

Standard setting or

 

Most significant bit set to 0.

7/8 bits, 1/2 stop

 

 

 

Baud Rate

1200

50–38400

 

 

 

Parity

None

Odd, Even, or None

 

 

 

Duplex

Full

Full or Half

 

 

 

nd Turn your terminal on or run your terminal emulation software. Then press [ENTER] on your keyboard; a prompt appears on the screen. The prompt varies depending on your current password level:

=>

Normal prompt

User=>

User Password has been entered

od Press [ENTER] on your keyboard a few times to verify that the UPS responds.

rd To control or monitor the UPS, simply type the desired command and press [ENTER].

Table 7 shows what keystrokes to use as you type commands or view displays. See Table 8 for more information on UPS commands.

Table 7. Keystroke Commands

Action

Key Sequence

 

 

Delete last character typed.

[BACKSPACE] or [CTRL]-[H]

 

 

Delete line.

[CTRL]-[X]

 

 

Pause displays that take more than one screen.

[CTRL]-[S]

 

 

Resume scrolling. (Turn Pause off.)

[CTRL]-[Q]

 

 

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

43

Page 49
Image 49
Powerware FE/QFE UPS manual DB-25 Port Settings, Keystroke Commands, Action Key Sequence