Startup for the FE and QFE 4.3–18 kVA UPS

To start the FE and QFE 4.3–18 kVA UPS, use the following steps:

hd Confirm the equipment to be protected by the UPS is powered off.

id For Plug-Receptacle UPSs: Verify that the AC input power is off at the service panel. Plug the UPS power cord into a power outlet.

NOTE If the plug does not match your receptacle outlet, ask your electrician to install the proper outlet.

For Hardwired UPSs: Confirm that an electrician has completed and tested the connection to the proper power source and connected your protected equipment according to the

po poOpo AUPP–18 kVA) Installation Guide. Confirm that your AC line disconnect switch and the UPS ON/OFF switch are both in the OFF position.

ld If your UPS has a DC switch, turn on the switch according to the UPS model:

4.3–7 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the ON position.

If you do not have an external battery cabinet(s): unlock the UPS front cover panel using the FERRUPS key and remove the front cover panel. Locate the DC switch behind the UPS front cover panel. If there is a precharge button next to the switch, press it for a few seconds. Turn the DC switch to the ON position and reinstall the UPS front cover panel.

10–18 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the ON position.

nd Starting the UPS on battery power: Use the key to turn the ON/OFF switch to the ON position. After a brief self-check, the BATTERY POWER and READY indicators illuminate. The UPS beeps every 20 seconds, indicating the UPS is running on battery power. The control panel scrolls this display: