Powerware FE/QFE UPS Command, Function, Date, Delay, Represents 2.5 mi lisec, Display, Format

Models: FE/QFE UPS

1 72
Download 72 pages 42.36 Kb
Page 51
Image 51

 

 

 

 

m

 

 

 

 

Command

Short

Password

delay. For a -second delay, enter delay 400.

Function

 

 

Form

 

 

 

date

da

None*

Displays[month]/[day]/[year]system time and date. To s t the date, enter ate

 

 

 

.

 

delay

dl

None

Delays next command when you nter number after delay. Each unit

 

 

 

represents 2.5 mi lisec

nds, so delay1would cause a 2.5 millisecond

 

 

 

 

 

display

d

Depends

Displays the values of

ne or more parameters (see Table 4 on page 32).

 

 

on

Format: display [parameter # or name] [parameter # or name]

 

 

parameter

Example: d1fullloadoldisplays the values of parameters 1, 16 and 21

 

 

password

 

 

 

 

 

 

extendedhistory

xh

None

Displays the minimum and maximum values of parameters 1 (Vac In),

 

 

 

2 (Vac Out), 7 (Vdc) and 5 (VA Out); the command then clears the

 

 

 

minimum and maximum values (see Table 4 on page 32).

 

 

 

 

format

f

None

Displays an 80-character line containing information on the FERRUPS’

 

 

 

status. CheckUPS II and other UPS monitoring software use this data.

 

 

 

 

help

? or he

None

Shows a list of terminal/computer commands.

 

 

 

 

history

h

None

Displays the minimum and maximum values of parameter 1 (Vac In); the

 

 

 

command then clears the minimum and maximum values.

 

 

 

 

identify

I

None

Shows Powerware’s address and telephone number and the software

 

 

 

version.

 

 

 

 

 

inverterlog

il

None

Displays the Inverter Log. See “Alarm and Inverter Logs” on page 62.

 

 

 

 

logs

l

None

Displays both the Alarm and Inverter Logs. See “Alarm and Inverter Logs”

 

 

 

on page 62.

 

 

 

 

 

off [time]

o [time]

None*

Shuts down the UPS a given number of seconds. The READY indicator

 

 

password

Example: Parameters 110displays parameters 1 through 10.

 

 

 

flashes until the UPS

huts down, and the UPS beeps five seconds before

 

 

 

shutdown. Example: OFF60shuts down the UPS in 60 seconds.

off [time] autostart

o [time]

None*

Shuts down the UPS in a given number of seconds (see above), and

 

a

 

restarts the UPS sho tly after power returns.

off cancel

o c

None*

Cancels timed shu down.

parameters

p

Depends

Shows a list of syst

parameters. See “Parameters” on page 32. You

 

 

on

can also displ y a range of parameters by entering the starting and

 

 

parameter

ending parameter number or name after the command.

*If you change parameter 39 to “Yes,” this command requires a User password.

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

45

Page 51
Image 51
Powerware FE/QFE UPS Command, Function, Date, Delay, Represents 2.5 mi lisec, Display, Extendedhistory, Format, Help, Logs