R

2700-I ACC Wood Insert

Installer’s Guide

6 Getting Started

A. Design and Installation Considerations

CAUTION

Check building codes prior to installation.

Installation MUST comply with local, regional, state and national codes and regulations.

Consult insurance carrier, local building, fire officials or authorities having jurisdiction about restrictions, installation inspection, and permits.

Before installing, determine the following:

B. Draft

Draft is the pressure difference needed to vent appliances successfully. When a appliance is drafting successfully, all combustion byproducts are exiting the home through the chimney.

Considerations for successful draft include:

Preventing negative pressure

Location of appliance and chimney

To be sure that your appliance burns properly:

During a low burn, the chimney draft (static pressure) should be approximately -.04 inch water column (W.C.)

Type of chimney connector to be used

·single wall, 6 inch (152mm) diameter, stainless steel, or

·double wall, 6 inch (152mm) diameter, stainless steel

Consult page 28 for clearances to combustibles

Power outlet located close by for optional blower

During a high burn the chimney draft should be approximately -.10 inch (W.C.)

Measure the W.C at 6 inches (152mm) above the top of the appliance after one hour of operation at each burn setting.

WARNING

Asphyxiation Risk.

Do NOT connect this unit to a chimney flue servicing another appliance.

Do NOT connect to any air distribution duct or system.

May allow flue gases to enter the house.

WARNING

Fire Risk.

Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:

Installation and use of any damaged appliance.

Modification of the appliance.

Installation other than as instructed by Hearth & Home Technologies.

Installation and/or use of any component part not approved by Hearth & Home Technologies.

Operating appliance without fully assembling all components.

Operating appliance without legs attached (if supplied with unit).

Do NOT Overfire - If appliance or chimney connector glows, you are overfiring.

Any such action that may cause a fire hazard.

Notice: Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance system caused by:

Inadequate draft due to environmental conditions

Downdrafts

Tight sealing construction of the structure

Mechanical exhausting devices

Overdrafting caused by excessive chimney heights

Ideal performance is with height of chimney between 14-16 feet (4.26-4.88m) measured from the base of the appliance.

December 15, 2009

7046-137C

Page 25

Page 25
Image 25
Quadra-Fire 7046-137C warranty Getting Started, Design and Installation Considerations, Draft