Quadra-Fire CB1200MI-MBK, CB1200I B. Clearance To Combustibles, UL and ULC, As A Built-In

Models: CB1200MI-MBK CB1200I

1 52
Download 52 pages 35.16 Kb
Page 9
Image 9
B. Clearance To Combustibles, UL and ULC

R

CB1200-I Pellet Insert

B. Clearance To Combustibles, UL and ULC

AS A BUILT-IN

Rear Shroud Kit is Required for Built-In Installation

A

D

C

B

 

B

C

 

 

 

 

E

0inch (0mm) Clearance to Exposed Section and Face Trim

Figure 9.1

A

Top of Shroud

Top Vent

3.0

76

 

 

Rear Vent

0

0

B

Sides of Inside Shroud

Top or Rear Vent

0

0

C

Back of Inside Shroud

Top Vent

2.5

64

 

 

Rear Vent

0

0

D

Vent Pipe to Combustible

Top or Rear Vent

3.0

76

INSTALLED AS A BUILT-IN UNIT

Shown with Rear Vent and Optional Outside Air

Combustible

 

Mantel

 

12 in.

Shown with Hopper Extended

 

(305mm)

 

 

6 in.

 

(152mm)

 

Rear Shroud

 

Optional Outside

 

Air

Figure 9.2

NOTICE:

Please note that while the minimum clear- ance for the termination cap is 6 inches (152mm) there is the possibly of soot buildup around the termination area. If this occurs we suggest to move the termination further away from the house to prevent it.

WARNING

Fire Risk.

Comply with all minimum clear- ances to combustibles as specified.

Failure to comply may cause house fire.

NOTE:

Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY.

Illustrations/diagrams are not drawn to scale.

Actual installation may vary due to individual design preference.

February 3, 2010

7014-188B