A. Mobile Home Installation

You must use a Quadra-Fire Outside Air Kit for installation in a mobile home.

1.An outside air inlet must be provided for the combustion air and must remain clear of leaves, debris, ice and/or snow. It must be unrestricted while the appliance is in use to prevent room air starvation which causes smoke spillage. Smoke spillage can also set off smoke alarms.

2.The combustion air duct system must be made of metal. It must permit zero clearance to combustible construc- tion and prevent material from dropping into the inlet or into the area beneath the dwelling and contain a rodent screen.

3.The appliance must be secured to the mobile home structure by bolting it to the floor (using lag bolts) in two places. Use the same holes that secured the appliance to the shipping pallet.

4.The appliance must be grounded with #8 solid copper grounding wire or equivalent, terminated at each end with an NEC approved grounding device.

5.Refer to Clearances to Combustibles and floor pro- tection requirements on pages 9 & 10 for listings to combustibles and appropriate chimney systems.

6.Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the the exterior of the structure.

7.Follow the chimney manufacturer’s instructions when installing the vent system for use in a mobile home.

8.Installation shall be in accordance with the Manufactur- ers Home & Safety Standard (HUD) CFR 3280, Part 24.

WARNING

Installation must comply with Manufactured Home and Safety Standard (HUD), CFR 3280, Part 24.

CAUTION

THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/ROOF MUST BE MAIN- TAINED

Do NOT cut through:

Floor joist, wall, studs or ceiling trusses.

Any supporting material that would affect the structural integrity.

CAUTION

Never draw outside combustion air from:

Wall, floor or ceiling cavity

Enclosed space such as an attic or garage

 

Spark Arrestor Cap

Storm Collar

 

 

Roof Flashing

Joist Shield/Firestop

Approved Class “L”

 

or “PL” Pellet Vent

Figure 17.1

WARNING

Asphyxiation Risk.

NEVER INSTALL IN A SLEEPING ROOM. Consumes oxygen in the room.

February 3, 2010

7014-188B