Quadra-Fire CUMBGAP-MBK warranty Installation Considerations, A. Hearth Protection Requirements

Models: CUMBGAP-MBK CUMPGAP-PMH

1 44
Download 44 pages 54.25 Kb
Page 11
Image 11
Installation Considerations

 

See page 6 for stove clearances

 

 

R

 

 

Cumberland Gap Wood Stove

 

 

 

 

4

Installation Considerations

 

 

 

 

 

A. Hearth Protection Requirements

FLOOR PROTECTOR: Floor protector must be non- combustible material, extending beneath heater and to the front/sides/rear as indicated. The floor must be a minimum of 1/2 inch (26mm) thickness ("k" value = 0.84, R value = 0.59) non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible floor is not sufficient. See Alternate Floor Pro- tection on page 12.

In USA installations, it is necessary to install a non- combustible floor protector at least 16 inches in front and 8 inches to both sides of the fuel loading doors. See *excep- tion below.

In Canada, similar floor protection must be provided 18 inches (450mm) in front and 8 inches (200mm) from the sides and rear of the stove. See *exception below.

*EXCEPTION: Non-combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and extend 2 inches (51mm) beyond each side.

SIDE FUEL DOOR LOCKED SHUT

Front Fuel

loading door

200mm (8")

 

 

 

 

39-1/8"

200mm

 

 

200mm

1371mm

 

 

 

 

 

 

 

 

 

 

 

 

(994mm)

 

 

 

 

 

 

 

 

(54")

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(8")

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

(8")

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

 

 

8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(200mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16" (406mm) from

 

 

 

 

 

 

 

 

 

 

 

fuel loading door

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

USA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450mm (18")

 

 

 

34-5/8"(879mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CANADA

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 11.1

 

 

1089mm (42-7/8") Minimum

 

 

Figure 11.2

 

BOTH FUEL DOORS ACCESSIBLE

Figure 11.3

Figure 11.4

 

 

 

 

 

 

 

 

 

November 5, 2010

7006-188G

Page 11

Page 11
Image 11
Quadra-Fire CUMBGAP-MBK warranty Installation Considerations, A. Hearth Protection Requirements, Side Fuel Door Locked Shut