| Cumberland Gap Wood Stove |
|
|
|
|
4 | Installation Considerations |
|
|
| |
|
|
A. Hearth Protection Requirements
FLOOR PROTECTOR: Floor protector must be non- combustible material, extending beneath heater and to the front/sides/rear as indicated. The floor must be a minimum of 1/2 inch (26mm) thickness ("k" value = 0.84, R value = 0.59)
In USA installations, it is necessary to install a non- combustible floor protector at least 16 inches in front and 8 inches to both sides of the fuel loading doors. See *excep- tion below.
In Canada, similar floor protection must be provided 18 inches (450mm) in front and 8 inches (200mm) from the sides and rear of the stove. See *exception below.
*EXCEPTION:
SIDE FUEL DOOR LOCKED SHUT
Front Fuel
loading door
200mm (8")
|
|
|
| 200mm |
|
| 200mm | 1371mm | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| (994mm) |
|
| |||||||||
|
|
|
|
|
| (54") | |||||||||||||||||
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| (8") | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| Minimum | (8") |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Minimum | ||||||||||
|
|
|
|
|
|
| 8" |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
| (200mm) |
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| ||||||||||||||
16" (406mm) from |
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
fuel loading door |
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
| USA |
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
| 450mm (18") |
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| CANADA |
|
| ||||||||
|
|
|
|
|
|
|
|
|
| ||||||||||||||
| Minimum |
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
Figure 11.1 |
|
| 1089mm | |
|
| |||
Figure 11.2 | ||||
|
BOTH FUEL DOORS ACCESSIBLE
Figure 11.3 | Figure 11.4 |
|
|
| |
|
|
|
|
|
|
November 5, 2010 | Page 11 |