Quadra-Fire CUMPGAP-PMH Cumberland Gap Wood Stove 5 Chimney Requirements, A. Venting Components

Models: CUMBGAP-MBK CUMPGAP-PMH

1 44
Download 44 pages 54.25 Kb
Page 18
Image 18
Cumberland Gap Wood Stove

R

Cumberland Gap Wood Stove

5 Chimney Requirements

A. Venting Components

Chimney Connector:

It is also known as flue pipe or stove pipe. The chimney connector joins the stove to the chimney. It must be a 6 inch (152mm) minimum diameter 24 gauge mild steel black or 26 gauge blued steel, or an approved air-insulated double wall venting pipe.

Thimble:

A manufactured or site-constructed device installed in combustible walls through which the chimney connector passes to the chimney. It is intended to keep the walls from igniting. Site constructed thimbles must meet NFPA 211 Standards. Prefabricated must be suitable for use with selected chimney and meet UL103 Type HT Standards. Follow instructions provided by the manufacturer for manufactured thimbles for masonry chimney and prefabricated chimneys.

B. Chimney Systems

Prefabricated Metal Chimney

Must be minimum 6 inch (152mm) diameter (ID) high temperature chimney listed to UL 103 HT (2100oF) or ULC S629M.

Must use components required by the manufacturer for installation.

Must maintain clearances required by the manufacturer for installation.

Refer to manufacturers instructions for installation.

NOTE: In Canada when using a factory-built chimney it must be safety listed, Type UL103 HT (2100oF) CLASS “A” or conforming to CAN/ULC-S629M, STANDARD FOR 650oC

FACTORY-BUILT CHIMNEYS.

ADDITIONAL REQUIRED PARTS FOR REAR INSTALLATION:

Chimney:

The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements specified in Section 5B.

Baffle Diverter: Shipped with appliance located inside firebox

Horizontal Flue Heat Shield, Part HTSHLD-7006: Not sup- plied, must be purchased from your local authorized dealer

 

 

 

Combustible Outside Wall

 

 

Listed

2" (51mm)

 

 

Chimney Pipe

 

 

Clearance

 

 

Chimney

 

 

Listed Chimney

 

 

Connector

 

Listed Cap

 

 

 

 

Maintain 2" (51mm)

To Stove

Insulated "T"

Clearance Through Eave

 

 

 

 

Wall Support

 

 

Trim Collar

Wall Spacer on

 

 

on Inside

 

 

Wall

Outside Wall

Flashing

 

 

Combustible

*

 

 

Ceiling

 

Insulated "T"

 

 

 

 

Chimney

 

 

 

Connector

 

 

 

 

*

 

 

 

*

Combustible Wall

 

Floor

 

 

 

Protector

 

*Refer to Clearances to Combustibles

 

 

Figure 18.1 Prefabricated Exterior Chimney

 

 

 

 

Listed

 

 

Listed Cap

 

Chimney

Attic

Maintain 2" (51mm)

 

 

Insulation

 

 

 

Combustible

 

 

 

Shield

Clearance

 

Storm Collar

 

Ceiling

 

 

 

 

 

Specified

 

 

 

 

Joists

 

 

Flashing

 

 

Clearance

 

 

 

 

 

 

 

 

 

Chimney

Ceiling

 

 

 

 

Support

 

 

 

 

Connector

Listed Chimney

 

 

 

 

 

 

 

To Stove

 

 

 

 

 

 

Ceiling Support

 

 

 

Combustible Wall

 

 

 

 

 

 

Chimney

*

 

 

 

 

Connector

 

 

 

 

 

 

 

 

 

 

 

 

*Refer to Clearances

 

 

*

 

 

to Combustibles

 

 

 

 

 

 

Floor

 

 

 

 

 

Protector

 

 

 

 

 

Figure 18.2 - Prefabricated Interior Chimney

Page 18

7006-188G

November 5, 2010

Page 18