Quadra-Fire QV32-A H1 H, Venting with Two 90 Elbows, Use SL D-Seriescomponents only, Natural Gas

Models: QV32-A QV36-A

1 42
Download 42 pages 34.68 Kb
Page 20
Image 20
VENTING WITH TWO (2) 90o ELBOWS

VENTING WITH TWO (2) 90o ELBOWS

NATURAL GAS

V (MIN.)

 

H + H1 (MAX.)

90o Elbow on Top

2 FT (610mm)

1 FT (305mm)

 

3 FT (914mm)

2 FT (610mm)

 

4 FT (1.22m)

3 FT (914mm)

 

6 FT (1.86m)

4 FT (1.22m)

 

8 FT (2.48m)

5 FT (1.52m)

 

16 FT (4.8m)

H + H1 MAX. = 16 FT (4.8m)

V + H + H1

MAX. = 40 FT (12.2m)

VENTING WITH TWO (2) 90o ELBOWS

PROPANE

V (MIN.)

H + H1 (MAX.)

90o Elbow on Top

NOT ALLOWED

1 FT (305mm)

2 FT (610mm)

 

2 FT (610mm)

4 FT (1.22m)

 

3 FT (914mm)

6 FT (1.86m)

 

4 FT (1.22m)

8 FT (2.48m)

 

5 FT (1.52m)

16 FT (4.8m)

 

H + H1 MAX. = 16 FT (4.8m)

V + H + H1 MAX. = 40 FT (12.2m)

H1

H

Note: There MUST be a 25% reduction in total H when using flex vent, except when using the simple up and out installation (see Figure 9).

Use SL D-Series components only.

Figure 15. Venting with Two 90° Elbows

V

20

Page 20
Image 20
Quadra-Fire QV32-A, QV36-A H1 H, Venting with Two 90 Elbows, Use SL D-Seriescomponents only, VENTING WITH TWO 2 90o ELBOWS