Quadra-Fire QV32-A Venting with three 90 elbows, Use SL D-Seriescomponents only, Natural Gas

Models: QV32-A QV36-A

1 42
Download 42 pages 34.68 Kb
Page 24
Image 24
Figure 19. Venting with three 90° elbows

V1

VENTING WITH THREE (3) 90o ELBOWS

NATURAL GAS

 

MODEL QV32-A

MODEL QV36-A

V (MIN.)

H + H1 (MAX.)

H + H1 (MAX.)

90o Elbow on Top

2 FT (610mm)

2 FT (610mm)

1 FT (305mm)

3 FT (914mm)

3 FT (914mm)

2 FT (610mm)

4 FT (1.22m)

4 FT (1.22m)

3 FT (914mm)

6 FT (1.86m)

6 FT (1.86m)

4 FT (1.22m)

8 FT (2.48m)

8 FT (2.48m)

5 FT (1.52m)

16 FT (4.8m)

16 FT (4.8m)

H + H1 MAX. = 16 FT (4.8m)

V + V1 + H + H1

MAX. = 40 FT (12.2m)

VENTING WITH THREE (3) 90o ELBOWS

PROPANE

 

MODEL QV32-A

MODEL QV36-A

V (MIN.)

H + H1 (MAX.)

H + H1 (MAX.)

90o Elbow on Top

NOT ALLOWED

NOT ALLOWED

1 FT (305mm)

2 FT (610mm)

2 FT (610mm)

2 FT (610mm)

4 FT (1.22m)

4 FT (1.22m)

3 FT (914mm)

6 FT (1.86m)

6 FT (1.86m)

4 FT (1.22m)

8 FT (2.48m)

8 FT (2.48m)

5 FT (1.52m)

16 FT (4.8m)

16 FT (4.8m)

H + H1 MAX. = 16 FT (4.8m)

V + V1 + H + H1 MAX. = 40 FT (12.2m)

V

H1

H

Use SL D-Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent, except when using the simple up and out installation (see Figure 9).

Figure 19. Venting with three 90° elbows

24

Page 24
Image 24
Quadra-Fire QV32-A Venting with three 90 elbows, Use SL D-Seriescomponents only, VENTING WITH THREE 3 90o ELBOWS, Propane