Quadra-Fire QV36-A H H1, Venting with three 90 elbows, Use SL D-Seriescomponents only, Propane

Models: QV32-A QV36-A

1 42
Download 42 pages 34.68 Kb
Page 23
Image 23
VENTING WITH THREE (3) 90o ELBOWS

VENTING WITH THREE (3) 90o ELBOWS

NATURAL GAS

V (MIN.)

H (MAX.)

H + H1(MAX.)

90o Elbow on Top

2 FT (610mm)

4 FT (1.22m)

1 FT (305mm)

3 FT (914mm)

6 FT (1.86m)

2 FT (610mm)

4 FT (1.22m)

8 FT (2.48m)

3 FT (914mm)

6 FT (1.86m)

12 FT (3.72m)

4 FT (1.22m)

8 FT (2.48m)

16 FT (4.8m)

5 FT (1.52m)

16 FT (4.8m)

16 FT (4.8m)

V + H + V1 + H1 MAX. = 40 FT (12.2m)

VENTING WITH THREE (3) 90o ELBOWS

PROPANE

V (MIN.)

H (MAX.)

H + H1(MAX.)

90o Elbow on Top

NOT ALLOWED

NOT ALLOWED

1 FT (305mm)

2 FT (610mm)

4 FT (1.22m)

2 FT (610mm)

4 FT (1.22m)

8 FT (2.48m)

3 FT (914mm)

6 FT (1.86m)

12 FT (3.72m)

4 FT (1.22m)

8 FT (2.48m)

16 FT (4.8m)

5 FT (1.52m)

16 FT (4.8m)

16 FT (4.8m)

V + H + V1 + H1 MAX. = 40 FT (12.2m)

H

H1

V1

Use SL D-Series components only.

Note: There MUST be a 25% reduction in total H when using flex vent, except when using the simple up and out installation (see Figure 9).

Figure 18. Venting with three 90° elbows

V

23

Page 23
Image 23
Quadra-Fire QV36-A H H1, Venting with three 90 elbows, Use SL D-Seriescomponents only, VENTING WITH THREE 3 90o ELBOWS