Quadra-Fire QV32-A Vent Termination Minimum Clearances, = Vent Terminal, X = Air Supply Inlet

Models: QV32-A QV36-A

1 42
Download 42 pages 34.68 Kb
Page 30
Image 30
= VENT TERMINAL

 

 

 

 

G

 

 

 

R

 

 

 

 

v

 

 

 

 

D

 

 

 

A

H

 

 

 

 

 

 

 

 

 

 

 

v

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

B

 

 

 

 

 

 

 

 

 

 

 

U.S.

 

 

 

v

 

B

 

 

 

 

v

B

(3 FT)

 

 

 

v

 

 

 

 

 

 

 

 

 

F

v

 

v

I

M

v

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

J or K

O

N

P

Q

(See Note 2)

V

= VENT TERMINAL

X = AIR SUPPLY INLET

A

=

12"

clearances above grade, veran-

 

 

(See Note 1)

da, porch, deck or balcony

B

=

12"

clearances to window or door

 

 

 

that may be opened, or to per-

 

 

 

manently closed window.

D*

=

18"

vertical clearance to ventilated

 

 

 

soffit located above the terminal

 

 

 

within a horizontal distance of 2

 

 

 

feet (60 cm) from the center-line

 

 

 

of the terminal

E*

=

18"

clearance to unventilated soffit

F

=

9"

clearance to outside corner

G

=

6"

clearance to inside corner

H

=

3 ft. (Canada)

not to be installed above a gas

 

 

 

meter/regulator assembly within

 

 

 

3 feet (90cm) horizontally from the

 

 

 

center-line of the regulator

I

=

3 ft. (U.S.A.)

 

 

 

6 ft. (Canada)

clearance to service regulator

 

 

 

vent outlet and electric service

*30” minimum for vinyl clad soffits.

= AREA WHERE TERMINAL IS NOT PERMITTED

J

=

9" (U.S.A.)

 

 

 

12" (Canada)

clearance to non-mechani-

 

 

 

cal air supply inlet to build-

 

 

 

ing or the combustion air in-

K

=

3 ft. (U.S.A.)

let to any other appliance

 

 

 

6 ft. (Canada)

clearance to a mechanical

 

 

 

air supply inlet

L**

=

7 ft

clearance above paved

 

 

(See Note 1)

sidewalk or a paved driveway

 

 

 

located on public property

M*** =

18"

clearance under veranda,

 

 

 

porch, deck or balcony

N

=

6”

non-vinyl sidewalls

 

 

12”

vinyl sidewalls

O

=

18

non-vinyl soffit and overhang

 

 

42”

vinyl soffit and overhang

P

=

8 ft.

 

 

QMIN

RMAX

1 cap

3 feet

2 x Q ACTUAL

2 caps

6 feet

1 x Q ACTUAL

3 caps

9 feet

2/3 x Q ACTUAL

4 caps

12 feet

1/2 x Q ACTUAL

QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL

**a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

***only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor.

NOTE 1: On private property where termination is less than 7 feet above a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap shield is suggested.

NOTE 2: Termination in an alcove space (spaces open only on one side and with an overhang) are permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum between termination caps. 2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap. 3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap.

Figure 31. Vent Termination Minimum Clearances

NOTE 3: Local codes or regulations may require different clearances.

NOTE 4: Termination caps may be hot. Consider their proximity to doors or other traffic areas.

WARNING: In the U.S: Vent system termination is NOT permitted in screened porches. You must follow side wall, overhang and ground clearances as stated in the instructions.

In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow all side walls, overhang and ground clearances as stated in the instructions.

Aladdin Hearth Products assumes no responsibility for the im- proper performance of the fireplace when the venting system does not meet these requirements.

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR KIT TO THE TOP OF THE EXTERIOR FIRESTOP (FOR ALL ROUND TERMINATION CAPS). IT IS STRONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT.

30

Page 30
Image 30
Quadra-Fire QV32-A, QV36-A manual Vent Termination Minimum Clearances, = Vent Terminal, X = Air Supply Inlet