VENTING WITH TWO (2) 90o ELBOWS

NATURAL GAS

V (MIN.)

H (MAX.)

 

90o Elbow on Top

2 FT (610mm)

1 FT (305mm)

3 FT (914mm)

2 FT (610mm)

4 FT (1.22m)

3 FT (914mm)

6 FT (1.86m)

4 FT (1.22m)

8 FT (2.48m)

5 FT (1.52m)

16 FT (4.8m)

H MAX. = 16 FT (4.8m) V + V1 + H MAX. = 40 FT (12.2m)

VENTING WITH TWO (2) 90o ELBOWS

PROPANE

V (MIN.)

H (MAX.)

 

90o Elbow on Top

NOT ALLOWED

1 FT (305mm)

2 FT (610mm)

2 FT (610mm)

4 FT (1.22m)

3 FT (914mm)

6 FT (1.86m)

4 FT (1.22m)

8 FT (2.48m)

5 FT (1.52m)

16 FT (4.8m)

H MAX. = 16 FT (4.8m) V + V1 + H MAX. = 40 FT (12.2m)

H

V1

V

Note: There MUST be a 25% reduction in total H when using flex vent, except when using the simple up and out installation (see Figure 9).

Use SL D-Series components only.

Figure 16. Venting with Two 90° Elbows

21

Page 21
Image 21
Quadra-Fire QV36-A, QV32-A manual MAX. = 16 FT 4.8m V + V1 + H MAX. = 40 FT 12.2m