Regency Installation, Clearances, B36X Clearance Requirements, Caution Requirements, C Ceiling

Models: B36X

1 64
Download 64 pages 45.68 Kb
Page 9
Image 9
CLEARANCES

INSTALLATION

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Caution Requirements

The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoff may NOT be

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk

if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

B36X Clearance Requirements

Clearance:

 

 

Dimension

Measured From:

 

A: Mantel Height (min.)

 

6-1/2" (165mm)

Top of Fireplace Opening

 

B: Sidewall

12" (304mm) on one side

Side of Fireplace Opening

 

C: Ceiling

 

36-34" (933mm)

Top of Fireplace Opening

 

D: Mantel Depth

 

 

12" (304mm)

14-1/2 " (368mm) from

 

 

 

 

 

 

 

Top of Fireplace Opening

 

E: Alcove Width

 

 

84" (2134mm)

Sidewall to Sidewall (Minimum)

 

F: Alcove Depth

 

 

36" (914mm)

Front to Back Wall (Maximum)

 

Notes:

0"

 

No Hearth Required

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Vent Clearances

to Combustibles

Horizontal Top

2" (51mm)

Horizontal Side

1-1/2 " (38mm)

Horizontal Bottom

1-1/2" (38mm)

Vertical Vent

1-1/2" (38mm)

Regency Bellavista™ B36X Gas Fireplace

9

Page 9
Image 9
Regency Installation, B36X Clearance Requirements, Minimum Vent Clearances to Combustibles, Caution Requirements