DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

16.5 Heater Pressure Switch

Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are colour coded for each pressure setting.

Carry out a commission after working on or changing a pressure switch.

See Page 21, Section 11.

WARNING

Carbon Monoxide Hazard

Use correct pressure switch specified for each model.

Use of incorrect pressure switch could cause unsafe condition.

Failure to follow these instructions can result in death or serious injury.

Pressure Switch

75

90

100

115

RG P/N

90439811

90439807

90439811

90439807

 

 

 

 

 

Colour Code

grey

brown

grey

brown

 

 

 

 

 

40

Page 46
Image 46
Roberts Gorden DAT100, DAT75, DAT90, DAT115 service manual Heater Pressure Switch, See Page 21, Section