DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 14: CONVERSION BETWEEN GASES 14.1 General
Conversion between gasses will require a change of burner injectors and the gas valve
14.2 Burner Conversion
Conversion of the burner assembly from one gas to the other is the same for all types of heaters.
1.Remove the burner compartment cover as shown on Page 37, Section 16.2.
2.Remove the connection between the gas valve outlet and the manifold. See Page 36, Section 16.1 for gas valve removal.
3.Remove the manifold from the burner assembly by removing the screws at the top and bottom. See Page 37, Section 16.2.1.
4.Remove the main burner injectors.
5.Replace with the injectors for the new gas ensuring a gas tight seal.
6.Refit all components in reverse order.
14.3 Gas Valves
All gas valves used on the DualAir® units have pressure regulators that may be set to operate on natural gas or LPG.
Conversion is carried out by
Ensure that the gas inlet pressure to the heater is correct for the new gas, and that the gas supply has been purged of the old gas.
30