Roberts Gorden DAT75, DAT90 CONVERSION BETWEEN GASES 14.1 General, Burner Conversion, Gas Valves

Models: DAT115 DAT100 DAT90 DAT75

1 52
Download 52 pages 54.64 Kb
Page 36
Image 36
SECTION 14: CONVERSION BETWEEN GASES 14.1 General

DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 14: CONVERSION BETWEEN GASES 14.1 General

Conversion between gasses will require a change of burner injectors and the gas valve re-commissioning to the new conditions.

14.2 Burner Conversion

Conversion of the burner assembly from one gas to the other is the same for all types of heaters.

1.Remove the burner compartment cover as shown on Page 37, Section 16.2.

2.Remove the connection between the gas valve outlet and the manifold. See Page 36, Section 16.1 for gas valve removal.

3.Remove the manifold from the burner assembly by removing the screws at the top and bottom. See Page 37, Section 16.2.1.

4.Remove the main burner injectors.

5.Replace with the injectors for the new gas ensuring a gas tight seal.

6.Refit all components in reverse order.

14.3 Gas Valves

All gas valves used on the DualAir® units have pressure regulators that may be set to operate on natural gas or LPG.

Conversion is carried out by re-setting the burner pressure to the value in the data table during commissioning. See Page 7, Section 4.3.

Ensure that the gas inlet pressure to the heater is correct for the new gas, and that the gas supply has been purged of the old gas.

30

Page 36
Image 36
Roberts Gorden DAT75, DAT90, DAT100, DAT115 CONVERSION BETWEEN GASES 14.1 General, Burner Conversion, Gas Valves