SECTION 15: TROUBLESHOOTING

15.6 Troubleshooting for Fan Contactor

START

Does main fan run

automatically

in heating mode?

Yes

No

Is power supply 400v at

 

No

Fault elsewhere

 

 

three phase and N at the

 

 

 

main terminal?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

Does fan run when white

No

Is there 230v at contactor

No

Press in overload reset

No

button of combination

thermostat is pushed in?

 

 

coil terminal A1 and A2?

 

button and retest.

 

 

 

 

 

 

 

 

 

Yes

 

 

 

Yes

 

Yes

 

 

 

 

 

 

 

 

 

 

Replace

 

 

Contactor faulty.

Overload operated. Check for

 

 

 

 

three phases at mains

 

combination thermostat.

 

 

 

Replace.

 

 

 

 

 

 

terminals, loose electrical

 

 

 

 

 

 

 

 

 

terminals and motor overload.

 

Wiring faulty or faulty

 

combination thermostat.

 

Investigate.

 

No

Is there 230v between

Has fuse 1 on the

terminals 96 and A1 on No

printed circuit board

the contactor?

blown?

Yes

Yes

Overload Faulty

Replace fuse and

investigate.

Replace.

 

Does fan motor run with

little or no air flow?

No

Check filters and

ducting for blockage.

Yes

Does fan run

as burner fires?

Yes

Does main fan run

automatically

in cooling mode?

Yes

Are fan belts

No

Is fan/motor rotation

No

Transpose two incoming

loose or broken?

correct?

phase connections.

 

 

Yes

 

 

 

 

 

Replace or tighten belts.

 

 

 

 

Relay R1 faulty.

NoReplace.

No

Does fan run at cooling

No

Relay R2 faulty.

stage 1 (T11 live)?

Replace.

 

Yes

 

 

Does fan run at cooling

No

Relay R3 faulty.

stage 2 (T12 live)?

Replace.

Yes

Fan Operating

TROUBLESHOOT ENDS.

No

If problems persist, contact ROBERTS GORDON® at Tel: +44(0) 190 249 8733 or www.rg-inc.com

For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.

Conduct Commissioning procedure as on Page 21, Section 11