Roberts Gorden DAT75, DAT90, DAT100, DAT115 service manual General Technical Data Table

Models: DAT115 DAT100 DAT90 DAT75

1 52
Download 52 pages 54.64 Kb
Page 12
Image 12
4.2 General Technical Data Table

DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

4.2 General Technical Data Table

 

Model

75

 

90

100

 

115

Fan Data

 

 

 

 

 

 

 

Designed Air Flow # with Clean Filters

m3/sec

 

2.88

3.7

 

Min Air Flow at Coil

m3/sec

 

1.66

2.60

 

Max Air Flow at Coil

m3/sec

 

3.71

5.34

 

Fan Unit

 

 

457-486 Double Inlet Belt Drive

 

Fan Pulley

mm PCD

2A x 180 / 2A x 200

2A x 180

 

Motor Pulley

mm PCD

2A x 100 / 2A x 95

2A x 112 / 2A x 118

Vee Belts

 

 

2 x A 63

2 x A 64

 

Electrical Data - All models need 400v 50Hz 3N supply. Single phase supply output for control circuit 230v 50Hz fused at 5 Amp. All alarm and status signals 230v 50Hz. Modulation input 0-10vDC.

Total Electrical Load

kW

 

3.3

 

 

5.4

Motor Size

kW

 

2.2

 

 

4.0

Full Load Current

A

 

4.45

 

 

7.5

Run Current at Designed Air Flow #

A

 

4.0 / 4.5

 

 

7.0 / 7.5

Start Current

A

 

23.0

 

 

24.0

Cooling Coil - DX

 

 

 

 

 

 

 

 

Max Cooling Load Split into Two Equal

kW

 

57.74

 

 

71.54

Circuits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inlet Connection

in

 

 

7/8 copper

 

 

Outlet Connection

in

1 3/8 copper

 

1 5/8 copper

Condensate Connection

ISO 7-R

 

 

 

1

 

 

Refrigerant

 

 

 

 

R407C

 

 

Design Temp. ON

°C Dry Bulb

 

27

 

 

25

°C Wet Bulb

 

19.4

 

 

18.07

 

 

 

 

Design Temp. OFF

°C Dry Bulb

 

14.66

 

 

13

°C Wet Bulb

 

13.72

 

 

12.3

 

 

 

 

Filters - All Models

 

 

 

 

 

 

 

 

All Models

 

Qty. 6 - Farr 30/30 grade 100 x 635 x 406

Initial Pressure Loss

mbar

 

 

 

0.4

 

 

Max. Recommended Pressure Loss

mbar

 

 

 

1.5

 

 

Physical Data

 

 

 

 

 

 

 

 

Weight

kg

612

 

621

 

638

 

647

 

NR dB(A)

 

65

 

 

72

Noise from Cabinet at 1 m

SPL dB(A)

 

68

 

 

67.5

 

NR dB(A)

 

68

 

 

77

Noise from Air Inlet at 1 m

SPL dB(A)

 

73

 

 

75

 

NR dB(A)

 

75

 

 

81

Noise from Air Outlet at 1 m

SPL dB(A)

 

76

 

 

77

Electrical load at 230v 50Hz measured by calculating from total run current of appliance.

* Do not exceed the maximum length of flue stated or heater may not operate properly. Reduce the maximum length stated by 1 m for each 90° bend installed.

**If minimum air flow requirements are not met then temperature limit devices will shut down the heater.