16.3 Ignition Electrode and Flame Probe.

DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

16.3 Ignition Electrode and Flame Probe.

Fan/Limit Thermostat

 

Burners

 

 

Secondary

 

Limit

 

Thermostat

Flame

Flame

Probe

Probe

Remove all

burner compartment

 

screws to remove

 

the burner

Remove

compartment and

Screw

access the

 

“Front View”.

 

Burner Compartment

Front Views

Manual background Ignition

Electrode

Ignition

Electrode

(3 mm)

.120"

spark

gap

Burners

To replace the ignition electrode or flame probe, remove the electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of the burner compartment.

Description

Part Number

Spark Electrode

90427411

Automatic Ignition Flame Probe

90439300

Burners (all models)

92000000