SECTION 10: WIRING AND ELECTRICAL INFORMATION

10.3 DAT Main Circuit Board Terminal Identification

Terminal

Use

Relay/Function

Operation

Number

 

 

 

 

 

 

 

 

 

Input for Remote Fan Opera-

Optional - Main Fan Runs from

1 Input or Output

External Fan Control

tion Output for Fan Operation

External Control

 

 

Monitor

 

 

 

 

 

 

 

2 Output

230 V to external control

 

230 V 50 Hz supply of external

 

thermostat or control

 

 

 

 

 

 

 

3 Input

Burner On

Burner Fires.

Burner Operates.

R1 energizes with gas valve

Fan Operates via R1

 

 

 

 

 

 

4 Output

230 V Burner ON Signal

 

Optional Remote Indication of

 

Burner ON.

 

 

 

 

 

 

 

5 Output

Neutral for Signals

 

 

& External Control

 

 

 

 

 

 

 

 

 

7 Output

230 V Burner Lockout Signal

 

Optional Remote Indication of

 

Burner Lockout

 

 

 

 

 

 

 

8 Input

Burner Lockout Reset from N

 

Optional Remote Burner Lock-

(5)

 

out Reset (must be from N)

 

 

 

 

 

 

 

Volt Free Safety Circuits for

Site Wiring to Condensers

DualAir® units contains Coil

 

Frost Thermostat, Coil Pres-

9 & 10

Normally Closed Controls

External Condensers

sure Switch & Auxiliary Contact

 

Break on Fault Position

 

 

on Contactor

 

 

 

 

 

 

 

 

230 V 1st Stage of Cooling

 

Burner OFF

11 Input

R2 On

Fan ON from R2

(Free Cooling)

 

 

Dampers Output to T16

 

 

 

 

 

 

 

 

 

 

Burner OFF

 

230 V 2nd Stage of Cooling

R2 OFF

Fan ON from R3

12 Input

Dampers Output to T15

Cooling Coil Stage 1

R3 ON

 

Output to Condenser 1 at T17

 

 

 

 

 

 

& 18

 

 

 

 

 

230 V 3rd Stage of Cooling

R3 ON

All input 12 Operations

13 Input

Cooling Coil Stage 2

Output to Condenser 2 at T19

R4 ON

 

 

& 20

 

 

 

 

 

 

 

 

230 V Output for Optional

 

14 = Neutral

14, 15 & 16 Output

From R2

15 = Recirculated Air

Damper

 

 

16 = Fresh Air

 

 

 

 

 

 

 

17 & 18

Volt Free Control Circuit

R3 ON

Normally Open Contact

Condenser 1

 

for Condenser 1

 

 

 

 

 

 

 

Volt Free Control Circuit

R3 ON

Normally Open Contact

19 & 20

R4 ON

Condenser 2

for Condenser 2

 

 

 

 

 

 

21 & 22 Output

230 V Output to

 

21 = L

Remote Dirty Filter Warning

 

22 = N

 

 

 

 

 

 

 

Volt Free Output to

Alternative Dirty Filter Indica-

Normally Open Contact

23 & 24

tion for BMS or DualAir® Con-

 

Remote Dirty Filter Warning

trol

for Dirty Filter Indication

 

 

 

 

 

 

 

25 & 26 Input

0 - 10 V DC Input for

T3 Must Be Live to Operate

0 V = Minimum Fire

Modulating Burner

Burner

10 V = Maximum Fire

 

 

 

 

 

17