Outdoor unit

ffA place free from the risk of combustible gas leakage. ffA place which can bear the weight of the unit.

ffA place which can bear the fixing strength of the outdoor unit. ffAvoid a place subject to oil (including machine oil). ffAvoid a saline place.

ffAvoid a place subject to sulfide gas (hot spring zone). (When installing the unit at such special environmental conditions, it may cause machine trouble. When it is unavoidable to use such places. It requires special maintenance.)

ffA place where the discharge air and noise of the outdoor unit do not disturb the neighborhood. (Take special care not to cause any inconvenience to your neighbors when installing the unit on the borderline with your neighborhood.)

ffA place where strong wind does not head against the air outlet of the outdoor unit. (If a strong wind heads directly against the air outlet at the time of cool operation, a safety device can be operated.)

ffDo not install the outdoor unit at an unstable place such as outer wall of an apartment or building. The outdoor unit may fall down, causing severe personal or property damage or loss.

❋❋ If there is any unavoidable reason to install the unit at such a place, take the following measures against the wind;

1)

When installing the unit at a roadside concentrated with

Wall

Strong wind

 

buildings, install it parallel with the road.

Air

 

 

outlet

2)

Install the unit so that the air outlet faces toward the wall at a

 

 

place such as rooftop, which may be subjected to strong wind.

 

Roof top

 

 

 

ffThe outdoor unit should be installed in accordance with the service space.

ENGLISH

More than 60cm

More than 50cm

Space for piping

and wiring

More than 30cm

The air intake faces toward the wall.

 

 

 

 

 

More than 50cm

 

 

 

 

 

Space for piping

 

 

 

 

 

and wiring

 

 

 

 

 

 

 

 

 

 

More than 30cm

More than 60cm

The air outlet faces toward the wall.