Electrical work

The electrical work should be performed by a specialist qualified for the work.

ffUse the three phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit (separately purchased by the user).

❋❋Avoid multiple connecting wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circuit.

ffBe sure to install circuit breaker (separately purchased by the user). ffBe sure to connect the grounding wire.

 

 

 

Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible

 

 

 

cord. (Code designation IEC:60245 IEC 66 / CENELEC:H07RN-F)

NOTE

 

1.Remove the screw on the electrical component box and remove the cover plate.

2.Route the connection cord through the side of the indoor unit and connect the cable to terminals.

3.Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.

4.Reassemble the electrical component box cover, carefully tightening the screw.

Wiring standard

 

Model

AP55M0

AP55M1

AP55M2

AF55GC1MA

AF55GP1MA

AF55GC1MB

AF55GP1MB

 

Series

 

Series

Series

Series

 

Series

 

Series

 

Series

 

 

 

 

 

 

 

Power

 

 

3~, 220V, 60Hz

3N~, 380V,

1P, 220V, 60Hz

 

1P, 230V, 60Hz

 

 

60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit breaker

Earth Leakage Circuit

Earth Leakage

 

 

 

 

 

 

 

Circuit Breaker

 

Earth Leakage Circuit Breaker (ELCB) 50A

 

 

 

 

Breaker (ELCB) 40A

(ELCB) 30A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric

 

Below 20m

 

4mm2

2.5mm2

 

 

 

10mm2

 

wire

 

Below 50m

 

6mm2

4mm2

 

 

 

16mm2

 

Allowable voltage

198~242V

342~418V

 

 

198~242V

 

Min. size of electric

 

 

 

 

Below 20m : 0.75mm2

 

 

 

 

wires from/to the

 

 

 

 

Over 20m : 1mm2

 

 

 

 

indoor/outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You must compress the solderless ring to the cable and then connect it to the main power terminal. CAUTION • Solderless ring selection

Silver solder

Thickness of cable (mm2)

B (mm)

d2 (mm)

2.5

Less than 9.5

More than 4.5

4

Less than 9.5

More than 4.5

6

Less than 9.5

More than 4.5

10

Less than 15

More than 8.4

16

Less than 16

More than 8.4

34

PAC MIRAGE HPCO-AR-PH_IBIM_05321A-01_EN.indd 34

2015-03-03 오후 4:39:40