Installation method

Installation procedures

1.The piping of this unit can be connected to the right, left, and rear side.

-- When you hit the area for piping connection slightly with a hammer, a hole is made.

Holes for piping connection (4 points)

Protective

Protective

 

piping cover

piping cover

Drain hose

Piping

 

 

Drain hose

 

Piping

When the hole on the wall is lower than the hole for piping connection.

When the hole on the wall is higher than the hole for piping connection.

2.Open the front panel and separate it from the unit.

-- Be careful of the power lines connected to control panel when removing.

3.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place. -- Allowable pipe length : Maximum 25m

-- Allowable pipe drop distance : Maximum 15m

-- Make no more than ten bending points on the pipe

❋❋When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant (R22) of 30g for each additional 1m.

If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the

CAUTION pipe length should be as short as possible (less than 25m).

Less than 10m

Outdoor

unit

Indoor unit

Outdoor

unit

Indoor unit

 

Fix the pipe

Lessthan10m

than6m

Outdoor

 

Less

 

unit

Indoor unit

 

S-TRAP

Fix the

(Every 10 m)

pipe

 