Installation method
Installation procedures
1.The piping of this unit can be connected to the right, left, and rear side.
Holes for piping connection (4 points)
Protective | Protective |
|
piping cover | piping cover | Drain hose |
Piping |
|
|
Drain hose |
| Piping |
When the hole on the wall is lower than the hole for piping connection.
When the hole on the wall is higher than the hole for piping connection.
2.Open the front panel and separate it from the unit.
3.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place.
❋❋When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant (R22) of 30g for each additional 1m.
If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the
CAUTION pipe length should be as short as possible (less than 25m).
Less than 10m
Outdoor
unit
Indoor unit
Outdoor
unit
Indoor unit |
| Fix the pipe |
Lessthan10m | than6m | Outdoor |
| Less | |
| unit |
Indoor unit
| ||
Fix the | (Every 10 m) | |
pipe | ||
|
40