IL•1F CANopen DS301

3 Basics

Reading data The client starts a read request by sending the index and subindex that point to the object or the object value whose value it wants to read.

The server confirms the request by sending the desired data. The SDO response contains the same index and subindex. The length of the re- sponse data is specified in the command code "ccd".

Client

 

 

 

 

 

 

 

 

 

 

 

Server

read request

 

 

 

0

 

1

2

3

4

5

6

7

 

 

 

 

 

 

COB-ID

ccd

Idx2 Idx1 Sidx

 

data

 

 

 

ccd= 40h

 

 

 

 

 

 

 

 

 

0

1

 

2

 

3

4

5

6

7

 

read response

 

 

 

 

 

COB-ID

ccd

Idx

2

Idx

1

Sidx

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ccd= 43h

 

 

 

 

 

 

data

 

 

 

ccd= 47h

 

 

 

 

 

 

data

 

 

 

 

ccd= 4Bh

 

 

 

 

 

data

 

 

 

 

ccd= 4Fh

 

 

 

 

 

data

 

 

 

 

 

Figure 3.14 Reading a parameter value

Unused bytes in the data field are shown with a slash in the graphic. The content of these data fields is not defined.

ccd coding The table below shows the command code for transmitting a read value. It depends on the message type and the transmitted data length.

Message type

Data length used

 

 

 

4

3

2

1 byte

 

 

bytes

bytes

bytes

 

 

 

 

 

 

 

 

read request

40h

40h

40h

40h

Request read value

Read response

43h

47h

4Bh

4Fh

Return read value

Error response

80h

80h

80h

80h

Error

Table 3.6 Command code for transmitting a read value

0198441113586, V2.01, 11.2008

Fieldbus interface

29