6 Operation

6.4.5Operating mode Homing

During the reference movement a limit switch or reference switch is ap- proached and then a new value is assigned to this position.

Before a reference movement is started, the parameters must be set by means of SDO write access to satisfy the requirements. See the product manual for detailed information on parameterization and on performing a reference movement.

To start a reference movement the following settings must be made in the R_PDO4:

Enter the type of reference movement in Ref16 (Ref32 has no sig- nificance here).

The available types of reference movement are described in the device manual.

In modeCtrl, enter operating mode 12h"Homing".

Toggle modeCtrl, bit 7, so the data is taken over by the slave.

Example A reference movement to the negative limit switch (LIMN) is to be per- formed; this is reference movement type 2.

Master <---> Slave

Trigger reference movement

R_PDO4

--->

drivectrl

modeCtrl

Ref16

Ref32

 

 

 

02h

92h

0002h

XXXXXXXXh

Reference movement runningx-

T_PDO4

<---

driveStat

modeStat8

 

p_act

err=0, xend=0

 

 

0006h

2h

 

XXXXXXXXh

Reference movement complete

T_PDO4

<---

driveStat

modeStat

 

p_act

xerr=0, xend=1

 

 

4006h

A2h

 

00000000h

 

Table 6.7

Reference movement

 

 

 

0198441113586, V2.01, 11.2008

Fieldbus interface

71