IL•1F CANopen DS301

8 Object directory

The time span for connection monitoring of an NMT master results from the time span "guard time" multiplied by the factor "life time", object Life time factor (100Dh).

The time span can be changed in the NMT state "Pre-Operational".

100Dh Life time factor

The object specifies the factor that, together with the time span "guard time", results in the time interval for connection monitoring of an NMT master. Within this period, the NMT slave device expects a monitoring request via node guarding from the NMT master.

life time = guard time * life time factor

The value "0" deactivates monitoring of the NMT master.

Object description

Index

100Dh

Object name

life time factor

Object code

VAR

Data type

Unsigned8

 

 

Value description

Subindex

00h, life time factor

Meaning

Time factor for the node guarding protocol

Access

read-write

PDO mapping

Value range

0...255

Default value

0

Can be saved

 

 

If there is no connection monitoring through the NMT master during the time interval "life time", #Variable:device-name# signals an error and switches to error state.

The time factor can be changed in the NMT state "Pre-Operational".

The time span "guard time" is set with the object Guard time (100Ch).

1015h Inhibit time emergency message

The object specifies the waiting time for the repeated transmission of

EMCY messages as a multiple of 100μs.

Object description

Index

1015h

Object name

inhibit time EMCY

Object code

VAR

Data type

Unsigned16

0198441113586, V2.01, 11.2008