Chapter 4 — Programming Considerations

Modbus

Name

Values

 

Description

Address

 

 

 

 

 

 

 

 

 

40033

MBP Status

0

This register is used to

 

 

to

communicate the last Invalid

 

 

3

MBP Status value. Possible

 

 

 

values are as follows:

 

 

 

0 No error since power

 

 

 

 

cycle

 

 

 

1

Invalid Global Cmd

 

 

 

 

Request Most likely the

 

 

 

 

slave address for the

 

 

 

 

MBP is > 16 and is

 

 

 

 

configured for Global

 

 

 

 

Cmd

 

 

 

2

Invalid Global Length

 

 

 

 

The host is not configured

 

 

 

 

to send enough Global

 

 

 

 

Data to support this

 

 

 

 

node’s Modbus Plus

 

 

 

 

address

 

 

 

3

Invalid Write Range

 

 

 

 

An MSTR Type 1 write

 

 

 

 

cmd was received

 

 

 

 

attemtpting to write into

 

 

 

 

the 40011 to 40100

 

 

 

 

address range. The cmd

 

 

 

 

was disregarded by the

 

 

 

 

MBP with a successful

 

 

 

 

response returned to the

 

 

 

 

host.

Note that this register is only cleared on power up, and will only be updated when a new error condition arises. Therefore be aware that a non-zero value will stay in the register after an initial error condition until the next power cycle.

40034

Not Defined

Reserved for future use

to

at this time

 

40100

 

 

24

Page 24
Image 24
SMC Networks 1560 user manual At this time