Chapter 3 — Hardware Setup

Contents

Switch SW 2 (cont’d.)

Function

Description

Details

 

 

 

 

 

 

 

 

 

 

 

Global Data

Enables the 1560-MBP

SW2-7

 

 

 

 

Base Control

to automatically gather

Off = Disable Global Data

 

the Control Word and

 

 

Base Control

 

 

Speed Reference

On = Enable Global Data

 

values from the

 

 

Base Control

 

 

selected Host Global

 

 

 

 

 

 

 

 

 

 

 

 

Database.

 

 

 

Important

 

 

 

 

 

 

 

 

When enabled, the

A maximum of 16 1560-MBP

 

 

units can be enabled in the

 

1560 will use two

 

 

Global Control Mode on one

 

words from the global

 

PLC network. These 16 units

 

database based on the

 

must be addressed within one

 

selected Modbus Plus

 

 

of the following ranges:

 

address (SW1-1 to 6).

 

 

 

 

 

1 to 16

 

 

 

 

 

 

 

 

 

 

When disabled, the

 

 

 

17 to 32

 

 

 

Host must write into

 

 

 

33 to 48

 

 

 

1560 unit's Modbus

 

 

 

49 to 64

 

 

 

register table at

 

 

 

 

 

 

 

 

addresses 40001/2 to

 

 

 

 

 

 

 

 

write the Control word

 

 

 

 

 

 

 

 

and speed reference

 

 

 

 

 

 

 

 

values

 

 

 

 

 

 

 

 

 

 

 

 

 

Modbus Plus

Selects the Modbus

SW2-1 to 6

 

 

 

Address

Plus Address for the

1

 

Address Bit 0

 

Value = 1

(1560-MBP

1560-MBP unit. Each

2

 

Address Bit 1

 

Value = 2

unit address)

node must have a

3

 

Address Bit 2

 

Value = 4

4

 

Address Bit 3

 

Value = 8

 

unique address. Note

 

 

 

5

 

Address Bit 4

 

Value = 16

 

that the addresses will

6

 

Address Bit 5

 

Value = 32

 

be one higher than the

6

5

4

3

2

1

Address

 

binary value selected by

 

off

off

off

off

off

off

1

 

the dip switches.

off

off

off

off

off

on

2

 

 

off

off

off

off

on

off

3

 

 

off

off

off

off

on

on

4

 

It is recommended that

off

off

off

on

off

off

5

 

address 1 not be used

off

off

off

on

off

on

6

 

off

off

off

on

on

off

7

 

to avoid possible

 

off

off

off

on

on

on

8

 

confusion when using a

off

off

on

off

off

off

9

 

local default address of

off

off

on

off

off

on

10

 

off

off

on

off

on

off

11

 

1 at a controller node

off

off

on

off

on

on

12

 

programming panel.

off

off

on

on

off

off

13

 

off

off

on

on

off

on

14

 

 

 

 

off

off

on

on

on

off

15

 

 

off

off

on

on

on

on

16

 

 

off

on

off

off

off

off

17

 

 

off

on

off

off

off

on

18

13

Page 13
Image 13
SMC Networks 1560 user manual Switch SW 2 cont’d