SMC Networks 1560 user manual SCANport

Models: 1560

1 44
Download 44 pages 55.53 Kb
Page 26
Image 26

Chapter 5 — Troubleshooting

NAME

Color

Status

Indication

 

 

 

 

 

 

Two Flashes

The node is hearing the token being

 

 

then OFF for

passed among other nodes, but is

 

 

two seconds

never receiving the token. Check the

 

 

 

network for an open circuit or defective

 

 

 

termination.

 

 

 

 

 

 

Three Flashes

The node is not hearing any other

 

 

then OFF for

nodes. It is periodically claiming the

 

 

1.7 seconds

token but finding no other node to

 

 

 

which to pass it. Check the network for

 

 

 

an open circuit or defective termination.

 

 

 

 

 

 

Four Flashes

The node has heard a valid message

 

 

then OFF for

from another node that is using the

 

 

1.4 seconds

same address as this node. The node

 

 

 

remains in this state as long as it

 

 

 

continues to hear the duplicate address.

 

 

 

If the duplicate address is not heard for

 

 

 

five seconds, the node then changes to

 

 

 

the pattern of one flash every second.

 

 

 

 

 

 

 

 

SCANport

Green

Steady

SCANport connection if OK

Status

 

 

 

 

Blinking

Check cable connections. Indicates that

 

 

 

 

 

the 1560-MBP unit is not able to link up

 

 

 

with the drive’s SCANport. Make sure

 

 

 

that the A-B device supports Datalinks if

 

 

 

the 1560-MBP Datalinks are enabled.

 

 

 

 

 

Red

Steady

The SCANport connection has faulted.

 

 

 

Check configuration switch settings,

 

 

 

SCANport cable connections, cycle

 

 

 

power. Contact ProSoft factory support

 

 

 

if problem persists.

 

 

 

 

26

Page 26
Image 26
SMC Networks 1560 user manual SCANport