SMC Networks 1560 user manual Appendix E, SCANport Datalink Operation

Models: 1560

1 44
Download 44 pages 55.53 Kb
Page 41
Image 41

Appendix E — SCANport Datalinks

Appendix E

SCANport Datalink Operation

(Excerpted from A-B Publication 1203-5.2 - May 1995)

In the following discussion, the term ‘Datalink’ is used

extensively. When configuring some SCANport devices, the

term ‘Adaptor I/O’ is used in place of Datalink.

A Datalink is a type of pointer used by some SCANport devices to transfer information between a SCANport communication interface (such as the 1560-MBP) and a SCANport device (such as a VFD, SMP3, etc.). Datalinks allow parameter values to be written when the Control Command and Reference are sent to the SCANport device. Datalinks also allow parameter values to be read whenever the Status and Feedback values are read from the SCANport device.

SCANport devices that support Datalinks have a group of parameters for Datalink configuration. These parameters are identified as ‘Datalink In’ and Datalink Out’ parameters. The Datalink functions are enabled by setting the appropriate dip switches on SW1 and by configuring the ‘Datalink In’ and Datalink Out’ adapter I/O parameters in the SCANport device.

Each Datalink consists of two 16-bit words of input and two 16-bit words of output. Each of the two input words can be configured to write to a different destination parameter inside the SCAnport device by setting the two ‘Datalink In’ parameters for that Datalink to the desired destination parameters. Similarly, each of the two output words is configured by setting the two ‘Datalink Out’ parameters for that Datalink.

If a Datalink is enabled the value of the parameters pointed to by the ‘Datalink Out’ parameters will be transferred to the 1560-MBP. Conversely, data values sent into the Datalink registers will be written to the parameter locations configured in the ‘Datalink In’ parameters. If a Datalink is not enabled, any data sent to the corresponding 1560-MBP data space will be ignored.

If no ‘Datalink In’ parameter is configured the SCANport device will ignore it. The same is true for a ‘Datalink Out’ parameter. A zero usually represents an un-configured Datalink.

41

Page 41
Image 41
SMC Networks 1560 user manual Appendix E, SCANport Datalink Operation