M4557 - Model 9210 Nitriding Controller
2.8Speed of Response
Typical T90 for combustion gas application is 30 seconds.
2.9Power Requirements Voltage: 24Vdc +/- 5% Power: 10W
2.10Gas Connection
The standard connections are captive seal compression fittings suitable
for 0.25" (or 6mm) diameter tube on the sample inlet and sample outlet. The tubing must be sturdy enough to withstand the slight compression applied by the tightened coupling. Metal, nylon or other rigid plastics are suitable. Rubber, PVC etc. are only suitable if a supporting insert is used. See figure 1 for inlet / outlet
78
Figure
2:
Sensor
4.0CALIBRATION
SSi Manual SERIES | Page 57 of 57 |