M4557 - Model 9210 Nitriding Controller

Internal Loop 2

Internal Loop 3

Instrument 1 – Instrument 25

The “Event Inst” selection will allow the user to set the events instrument:

Internal

Instrument 1 – Instrument 25

The “Quench Inst” selection will allow the user to set the quench instrument:

Internal Loop 1

Internal Loop 2

Internal Loop 3

Instrument 1 – Instrument 25

The “End of Quench Event” will allow the user to set the end of quench event. It can be event 0 through event 14.

The “Quench Speed Event” will allow the user to set the quench speed event. It can be event 0 through event 14.

The “Quench Run Event” will allow the user to set the quench run event. It can be event 0 through event 14.

The “Nitrider Bias” selection can be used to adjust the % Dissociation/Kn reading to match Pipette or Metallurgical readings. Setting this value to 5.0 will increase the reading from 20 to 25, whereas setting the value to –5.0will decrease the reading from 20 to 15. This can range from –10.0to 10.0

The “SSI Flow Signal” selection will allow the user to set the flow signal. It can be either Analog or Digital/485.

The “End Recipe Events Clear” selection will allow the user to clear out the events at the end of a recipe. It can be either Yes or No.

Default Wait Limits

Parameter

Value

Temperature Wait Limit

15 °

Atmosphere Wait Limit

10

 

 

 

 

The wait limits are used in the recipe programming. A wait limit allows the program to move to the next step once the process variable (or the actual furnace) has gotten to within the default wait limits that are indicated on this screen.

Highlighting your choice to be changed and pressing the Enter key moves you to a numeric keypad that allows you to enter a new value by touching the appropriate keys. The Temperature Wait Limit can range from 0 to 50 degrees. The Atmosphere Wait Limit can range from 0.00 to 0.49. Pressing the Esc key takes you back to the Menu screen.

Furnace Name

Parameter

Value

Furnace Name

Nitrider

PV1 Name

Dissociation

PV2 Name

Temperature

PV3 Name

Back Pressure

 

 

Select the parameter to edit and press the Enter key to display an alphanumeric keyboard. Enter the name that you wish to be displayed.

SSi Manual SERIES 9210-M4557-Nitriding

Page 27 of 27

Page 27
Image 27
SSI America 9210 user manual Internal Instrument 1 Instrument, Default Wait Limits, Furnace Name