Chapter 7: Troubleshooting

7-1

General Troubleshooting

 

Problem

 

Possible Cause

Solution

The control panel doesn’t light up at

The control panel is not turned on.

Turn on the control panel.

all

 

 

 

 

 

 

 

 

 

The external disconnect

Close the switch (on).

 

 

(recommended) in the dedicated

 

 

 

circuit is open (off).

 

 

 

Fuse/circuit breaker in the power

Replace/reset.

 

 

drop is blown/tripped.

 

 

 

Control power switch is broken.

Replace.

The touch screen display doesn’t

Fuse in display is blown.

Replace.

come on when the control panel is

Loose wiring to display.

Repair.

powered up.

 

 

 

 

Power supply problem.

Check 24V DC source.

 

 

 

 

Display is faulty.

Replace.

A pump package doesn’t run, even

The motor overload has tripped.

Reset the overload and check the

though it is on-line and its indicator

 

motor for the proper amp draw on

is lit.

 

 

tag.

 

 

Hoppers not assigned/no demand.

Check hopper assignment, verify

 

 

 

hoppers are online.

 

 

Main fuse in power drop or optional

Replace the fuse.

 

 

fused disconnect has blown.

 

 

 

Motor contact is faulty.

Repair or replace as required.

A vacuum receiver is being by-

The hopper is off-line.

Use the controller to put the vacuum

passed in the loading cycle.

 

receiver on-line.

 

 

Faulty level sensor or loose.

Check level sensor/wiring.

 

 

 

 

 

 

The convey time for the hopper is

Use the controller to enter a longer

 

 

set to zero.

convey time.

 

 

The field-installed station bypass

Normal operation. Set the switch so

 

 

switch is simulating a Bin Full

the vacuum receiver is back in the

 

 

condition.

loading sequence.

 

 

The field-installed station bypass

Repair, replace, or re-wire.

 

 

switch is bad or mis-wired.

 

 

 

The vacuum receiver was assigned

Repeat the setup procedure and

 

 

to the wrong pump during setup.

verify that the pump is on.

Vacuum hoppers are overfilling.

Conveying times are too long (Time

Time the vacuum receiver (s) during

 

 

Fill Mode only).

loading, and set the conveying times

 

 

 

to a few seconds less.

 

 

Maximum conveying times are too

Check proximity sensors for proper

 

 

long, and the PLC does not

operation and proper wiring to the

 

 

recognize the Vacuum Receiver Full

PLC. Repair as needed. Reset the

 

 

Proximity Switch(es).

conveying times to a reasonable

 

 

 

value, and adjust as needed.

 

 

Special convey is enabled and

Disable special convey. Reduce

 

 

convey time is too long.

convey time.

Power is present but control will not

Check PLC. See if fault light is on.

Reload software. See page 43.

function.

 

Loose communication cable between

Verify wiring.

 

 

PLC and display

 

2–Pump 20-Station Controllers

Troubleshooting

43 of 51