6.TROUBLESHOOTING
No output power or Lower output
When engine is running,
check if Overload Lamp is activated
Turned off
Turned on
Remove any electric load equipment that is connected
※Once stop the engine, and reset the overload warning
When engine is running,
check if the Pilot Lamp is turned on Voltage exceeds rated range
Turned off
Within the rating
Measured resistance value
Red
White
Blue
Generator
Confirm the engine revolutions (turn the APS sw to OFF) correct revolution 4100~4300rpm
Low, High
Go to the "Engine does not start (Start failure)" (refer to p. 44)
Measured resistance value between
) (Refer to the figure below) | |
Abnormal
Change the generator
Change INV C/U
<Resistance value of the generating main body for reference>
|
|
| Unit : Ω |
| Red - Blue | Blue - White | White - Red |
|
|
|
|
AC120V | 1.2 | 1.2 | 1.2 |
AC230V/240V | 4.2 | 4.2 | 4.2 |
|
|
|
|
|
| Surrounding temperature 20℃ |
– 42 –