INSTALLING THE VTL VALUE APPLIANCE IN AN EQUIPMENT RACK

1.Before you start, select the lowest possible position in the rack, and deploy the rack’s anti-tilt bar.

A top-heavy system tips over easily. So always load equipment into a rack from the bottom up and always place the heaviest equipment as low as possible. Always use the anti-tilt bar to keep the rack from tipping during installation. See the service label on the VTL Value appliance cover and/or the label on the rack.

2.Place the paper, rack-mount template (E below) in the selected position.

The rack-mount template ships with the slide-rail assemblies. It is the same height as the appliance (four rack-units—4U) and is marked with four arrows that show the location of the rail mounting screws. In a rack with 3 mounting holes per rack unit (as in the illustration), the template covers 12 holes.

 

 

E

4 U

 

4 U

F

3.Use the arrows on the template to select the rack mounting hole that will take the top slide-rail mounting screw (F above).

In the illustration above, the installed position of the slide rail is shown in pale gray.

6 VTL Value Hardware Installation Guide • Aug 2007